P00095

GIPAM – 2200

GIPAM-2200 series are multifunction microprocessorbased protection equipments suitable for all types of application such as distribution feeders. It can be also be used for management backup protection of incomings, feeders, transformers and high tension motors.

  • Reviews (0)
  • Features
  • Characteristics

Reviews

There are no reviews yet.


Be the first to review “GIPAM – 2200”

Features

  • 3 types of model for various protection functions
  • Easy GIPAM-2200 Setting
  • EVENT & FAULT RECORDING
  • Sequence of Event(SOE) Function
  • display a vector diagram
  • Select Before Operating(SBO) and Check Before Operating(CBO) Function
  • Various Communication Compatibilities
  • TRIP LOGIC and SEQUENCE
  • TRIP CIRCUIT SUPERVISION (TCS) & TRIP RELAY SUPERVISION (TRS)
  • CIRCUIT BREAKER FAILURE (CBF)
  • PT(VT) FAILURE

Characteristics

GIPAM-2200 F
Protection Operating part Setting range Operating time Note
Setting Curves
OCR (50/51) Instanta
neous
Low set OFF, 1.0~32.0In/0.1In Low: 0.05~300.00s / 0.01s
High:40ms and below
Definite
High set
Time delay OFF, 0.10~10.00In/0.01In 0.05~1.20 / 0.01
0.05~300.00s / 0.01s
Inverse
Definite
DT, SI, VI, EI, LI
OCGR
(50/51N)
Instanta
neous
Low set OFF, 0.1~8.0In/0.02In Low: 0.05~300.00s / 0.01s
High:40ms and below
Definite
High set
Time delay OFF, 0.02~2.00In / 0.01In 0.05~1.20 / 0.01
0.05~300.00s / 0.01s
Inverse
Definite
DT, SI, VI, EI, LI
NSOVR
POR (47)
Time delay Low set OFF, 0.1~1.0Vn / 0.1Vn 0.05~10.00s / 0.01s Definite V2=1/3 (VR + a2VS + aVT)
a=1∠120?, a2=1∠ 240°
High set
UVR (27) Time delay 0.20~1.00Vn / 0.01Vn 0, 0.05~10.00s /0.01s Definite
OVR (59) Time delay Low set OFF, 0.8~1.6Vn / 0.01Vn 0.05~10.00s / 0.01s Definite
High set
OVGR (64) Instantaneous OFF, 11~80V/1V Inst, 50~250ms / 5ms Definite DT, SI
Von=190V or 190 / 3V
Inst : 40ms and below
Time delay OFF, 11~80V/1V 0.05~1.00 / 0.01
0.05~300.00s / 0.01s
Inverse
Definite
NSOCR (46) Instantaneous OFF, 0.1~1.0In / 0.02In Inst, 50~250ms /5ms Definite DT, SI, VI, EI, LI
Time delay OFF, 0.1~1.0In / 0.01In 0.05~1.00 /0.01
0.05~10.00s / 0.01s
Inverse
Definite
Inst : 40ms and below
SGR (67G)
DGR (67N)
Time
delay
Zero-phase
current
isolated
system
0.9~6mA / 0.1mA
(Ion=1.5mA)
0.05~10.00s / 0.01s Definite Vo > Vos
Io > Ios
(Vo) -(Io) ≤ RCA + 87°
(Vo) -(Io) ≥ RCA - 87°
grounded
system
0.02~2.00Ion / 0.01Ion
(Ion=5A)
Zero-phase
voltage
11~80V/1V
(Von=190V, 190/ 3V)
Relay
characteristic
angle
0°~90°/5°
THR (49) Hot 0.2~1.2In/0.01In τh : 2.0~60.0min /0.5min t = τh·ln t : operating time
k : multiple factor
Cold τc : 2.0~60.0min /0.5min t = τc·ln (0.8~1.2/0.05)
τ: thermal constant
Stall/Lock
(48/51LR)
Time delay Stall OFF, 0.2~10.0In / 0.01In 0.05~300.00s / 0.01s Definite Start time range
1.0~300.0s / 0.1s
Lock OFF, 0.2~10.0In/0.01In 0.05~1.00 / 0.01
0.05~300.00s / 0.01s
Inverse (VI, EI)
UCR (37) Time delay 0.1~0.9In/0.02In 0.1~10.0s /0.01s Definite
NCH (66) Start