GIPAM-115 Digital Integrated Protection & Monitoring Equipment GIPAM is a multifunction, microprocessor-based protection equipment suitable for all types of applications such as distribution feeders. It can be also be used for management and backup protection of buses, transformers, and power lines. Drawout structure for panel-flush mounting User-friendly front panel to monitor, program, and test the GIPAM Data communication with a host computer

  • Reviews (0)
  • Features
  • Ratings

Reviews

There are no reviews yet.


Be the first to review “GIPAM – 115FI”

Features

Protection
  • Multi-functions offering a wide choice of protective options
    • OCR, 50/51
    • OCGR, 50/51N
    • OVR, 59
    • UVR, 27
    • OVGR, 64G
    • SGR, 67G
    • POR, 47
  • Broad setting ranges
  • All types of curves provided
    • SI, Standard inverse time delay
    • VI, Very inverse time delay
    • EI, Extremely inverse time delay
    • LI, Long inverse time delay
    • DI, Definite time delay
  • Logging of fault current and voltage for each phase
Metering and Monitoring
  • Acquisistion, visualization and storage of electrical data
    • Volt, Amepre, Watt, Zero phase volt, VAR, Watthour
    • VARH, Power factor, Frequency, Cumulative operating time
    • Number of operations closing and opening status
    • Digital displaying of each fault information
  • Broad setting ranges
  • Displaying status via digital LCD and analog Bar graph for better visualization
  • Offering operation reliability
    • Continuous monitoring and autodiagnostics systems through microprocessor technology
Communication
  • Modbus/RS-485
  • I-NET / LS customized protocol

Characteristics

Protection function
Functions Operation element Setting range Operating time Note
Setting range Characteristics
OCR
(50/51)
Instantaneous OFF, 2~24In / 1In 0.04~60.0s / 0.01s Definite time
Time delay OFF, 0.2~10.0In / 0.1In 0.05~1.20 / 0.01 Definite time 3 types
Inverse time 4 types
D2, D4, D8
SI, VI, EI, LI
OCGR
(50/51N)
Instantaneous OFF, 0.5~8.0In / 0.5In 0.04~60.0s / 0.01s Definite time Block time :
Time delay OFF, 0.1~0.5In / 0.02In 0.1~60.0s/0.1s Definite time 3 types
Inverse time 4 types
0.1~60.0s/0.1s
OVR(59) Time-delay(high) OFF, 0.80~1.60Vn / 0.02Vn 0.1~60.0s / 0.01s Definite time
Time-delay(Low) OFF, 0.80~1.60Vn / 0.02Vn 0.1~60.0s / 0.01s Definite time
UVR(27) Time-delay(high) OFF, 0.20~0.90Vn / 0.02Vn 0.1~60.0s / 0.01s Definite time Outage lock :
Time-delay(Low) OFF, 0.20~0.90Vn / 0.02Vn 0.1~60.0s / 0.01s Definite time (below 15V)
OVGRM
(64G)
Time-delay(high) OFF, 0.10~0.40Von / 0.02Von
(Von=190V)
0.1~60.0s / 0.01s Definite time
Time-delay(Low) OFF, 0.10~0.40Von / 0.02Von
(Von=190V)
0.1~60.0s / 0.01s Definite time
SGR
(67G)
Zero-phase
current
OFF, 0.6~3.6Ion / 0.2Ion (Ion=1.5mA) 0.1~60.0s / 0.01s Definite time
Zero-phase
voltage
0.10~0.40Von / 0.02Von
(Von=190V)
Relay
characteristic
angle
45°fixed
POR(47) Time-delay(high) OFF, 5~100% / 1% 0.1~60.0s / 0.01s Definite time
Time-delay(Low) OFF, 5~100% / 1% 0.1~60.0s / 0.01s Definite time
Measurement functions
Parameters Display Accuracy Remarks
Voltage, V AC 0.5~414,000V
Bar graph 0~120%
±0.5% Va, Vb, Vc
Vab, Vbc, Vca
Current, A AC 0.05~7,200A ±0.5% Ia, Ib, Ic
Zero-phase voltage, Vo 0~190(V)
Bar graph 0~120%
- Vo, Vo_max(peak)
Active power, Watts 0~9,999MW
Bar graph 0~120%
±1.0%
Reactive power, Vars 0~9,999MVar ±1.0%
Active energy, Wh 0~999,999MWh
Bar graph 0~120%
±1.0%
Reactive energy, Varh 0~999,999MVarh
Bar graph 0~120%
±1.0%
Power factor, PF Lead/Lag 0~100% ±1.0%
Frequency, F 45~65Hz ±0.5%

Ratings

Ratings
Type Specification
Wiring 1P3W, 3P3W, 3P4W
Input Frequency 60Hz/50Hz
Voltage PT 110V
GPT 190V, 190/ 3V
Current CT 5A
ZCT 200/1.5mA
Control Voltage AC/DC 110V/125V
Power Consumption Max. 30W
Burden PT Max. 0.5VA
CT Max. 1.0VA
Input Contact