P00103

GIMAC – Ⅰ

Convenient cubicle system, monitoring accurate values -Various measurement item -Control function -Various marking function -Communication function (I-net protocol)

  • Reviews (0)
  • Features
  • Characteristics

Reviews

There are no reviews yet.


Be the first to review “GIMAC – Ⅰ”

Features

  • Various measurement functions
    High accuracy (0.3%)
  • Compact size (144×144×85mm)
    - DIN 96 & ANSI"4 cutout size
  • Wide voltage range
    - AC 10 ~ 452V
  • MODBUS/RS-485
  • Control voltage AC/DC 88~264V
  • Protecting mis-wiring

Characteristics

Characteristics
NO EX Accuracy(%) Remarks
Voltage Vavg ±0.3% -
Vab, Vbc, Vca ±0.3% -
Va, Vb, Vc ±0.3% -
Current lavg ±0.3% -
la, lb, lc ±0.3% -
Load factor la, lb, lc - -
Phase ∠VabVbc, ∠VabVca - ±0.5° 3P4W
∠Vabla, ∠Vablb, ∠Vablc - ±0.5° 3P4W
∠VaVb, ∠VaVc - ±0.5° 3P4W
∠Vala, ∠Vblb, ∠Vclc - ±0.5° 3P4W
Power P ±0.5% IEC 1036
Pa, Pb, Pc - ±0.5% IEC 1036
Q ±0.5% IEC 1036
Qa, Qb, Qc - ±0.5% IEC 1036
S ±0.5% IEC 1036
Sa, Sb, Sc - ±0.5% IEC 1036
Energy Wh ±0.5% IEC 1036
Varh ±0.5% IEC 1036
rWh - ±0.5% IEC 1036
rVarh - ±0.5% IEC 1036
VAh ±0.5% IEC 1036
Frequency F(Hz) 0.05Hz -
Power factor PF + : Lag
PFa, PFb, PFc - - : Lead
DPFa, DPFb, DPFc -
THD THD(V) - - Va(ab), Vb(bc), Vc(ca)
THD(I) - - Ia, Ib, Ic
Harmonics 1st ~ 15th Harmonics (V) - - Va(ab), Vb(bc), Vc(ca)
1st ~ 15th Harmonics (I) - - Ia, Ib, Ic
Demand Demand W - - -
Demand la, lb, lc, lavg - - -
MAX max la, max lb, max Ic, max lavg - - -
max Va(ab) THD, max Vb(bc) THD
max Vc(ca) THD - - -
max la THD, max lb THD,
max lc THD - - -
max W - - -